E-AYY
Power distribution cables in power stations, industrial installations and switchgears, as well as in local mains. For fixed installation underground, in interior premises, cable ducts, in the open air, in water – as permitted by the local building regulations – if no risk of any mechanical damage is to be expected.
- inner covering: EPDM or plastic tape
- sheathing material: PVC black, UV resistant
Download: E-AYY - datasheet
Conductor material:
bare aluminium
Conductor construction:
RM, RE, SM, SE
Insulation:
PVC
Sheathing material:
PVC black, UV resistant
Nominal voltage Uo:
0,6 kV
Nominal voltage U:
1 kV
Test voltage:
4 kV
Fire resistance:
flame retardant EN 60332-1-2
Max. operating temperature:
70°C
Min. operating temperature:
-50°C
Max. short circuit temperature:
max +160°C/5s
Bending radius:
15xØ of cable (single core) / 12xØ of cable (multi core)