35-AVXEKVCVE
Single-core, distribution cable for outdoor and indoor use in 3-phase formation. Installation in pipes and ground/air. Cables meet requirements PNE 34 76 25 can be used in environments IV,V and VI according to PNE 33 0000-2. Product information
stranded, round, compacted aluminium acc. to ČSN EN 60228, class 2 with resistance against moisture penetration
XLPE, thickness 8,0 mm
PE, black or red
10xD
annealed copper wires and copper tape spiral counter
semi–conductiong water blocking tape
extruded
extruded, bonded
In continuous operation max. +90 °C on conductor. Min. cable temperature during installation: –20 °C and below 0 °C special measure should be taken.
180 kV
15xD
aluminium laminate bonded to sheath
- 35-AVXEKVCVE 20_35 (40,5) kV en-cz.pdf (341 views)