NHXCH FE180/E90
For installation in dry and wet rooms, also for direct bedding in concrete but not for direct burial in ground and not for use in water. The cable has improved flame retardant and may be used in public buildings with high safety requirements. Cables are halogen free, low smoke density and are fire resistant according to VDE 0472 part 814 (180 min., = IEC 60331). Furthermore, the cable passed the test of 90 min. circuit integrity according to DIN 4102 part 12 (E90) for all so called standard-installation systems (ladder,tray and ceiling) and is suitable for installation in fire alarm systems, safety lightning and other emergency electrical supply systems according to VDE 0108.
Product information
FRNC power cable NHXH FE180/E90 acc. to VDE 0266
bare copper
class 1, from 25 mm² class 2
FRNC compound HI1
FRNC-compound HM1
VDE 0482-266-2-4/IEC60332-3-24
90 °C
-5 - +70 °C
12 x DA
orange (RAL 2010)
0,6 kV
1 kV
4 kV
colours acc. VDE 0293 (HD308)
DIN EN 50267/IEC 60754
DIN EN 61034/IEC 61034
FE180
E90
1,2 kV